After power off, the swing gate machine is not operating properly. How to solve the problem? The swing gate may have some minor faults due to the instability of the power supply or the power failure. As a result, the swing gate cannot work normally. It is helpful for you to remove the common faults.
One: After the power switch is turned off, the pendulum swing arm does not operate normally and the pendulum arm is not limited. After the power is restored, the pendulum arm is reversed.
Solution:
1. Check the battery voltage (not less than DC9V);
2. Check if the circuit is loose or unwelded. Check the voltage output (DC12V) of the MA and MB terminals of the CON1 terminal of the power-down control board. Otherwise, the power-off control board is damaged.
3. Detect left and right open-position limit photoelectric switches and mainboards, respectively.
4. If the clearance of the movement is too large, the swing arm will cause the light block to move. After the swinging power is turned on, the limit signal is not detected and the motor is reversed. Use a dark opaque object to cut off the lamp on the lower limit photoelectric switch. If it can light, the limit switch is normal.
The above are two common troubleshooting methods after power failure in the Sino-Kun channel. It is hoped to help you. If a swing fault occurs, it is best to contact the swing gate manufacturer technician directly for assistance.
2: After the power is turned off, the gate brake will not operate and it will not stop.
Solution:
1. Check the battery voltage is normal (voltage not less than DC9V);
2. Check the gate line is loose or off;
3. Check the voltage output (DC12V) of the two terminals MA and MB of the CON1 terminal, and determine that the power-off control board of the swing switch is damaged.
One: After the power switch is turned off, the pendulum swing arm does not operate normally and the pendulum arm is not limited. After the power is restored, the pendulum arm is reversed.
Solution:
1. Check the battery voltage (not less than DC9V);
2. Check if the circuit is loose or unwelded. Check the voltage output (DC12V) of the MA and MB terminals of the CON1 terminal of the power-down control board. Otherwise, the power-off control board is damaged.
3. Detect left and right open-position limit photoelectric switches and mainboards, respectively.
4. If the clearance of the movement is too large, the swing arm will cause the light block to move. After the swinging power is turned on, the limit signal is not detected and the motor is reversed. Use a dark opaque object to cut off the lamp on the lower limit photoelectric switch. If it can light, the limit switch is normal.
The above are two common troubleshooting methods after power failure in the Sino-Kun channel. It is hoped to help you. If a swing fault occurs, it is best to contact the swing gate manufacturer technician directly for assistance.
2: After the power is turned off, the gate brake will not operate and it will not stop.
Solution:
1. Check the battery voltage is normal (voltage not less than DC9V);
2. Check the gate line is loose or off;
3. Check the voltage output (DC12V) of the two terminals MA and MB of the CON1 terminal, and determine that the power-off control board of the swing switch is damaged.